Features of Products
SZ10 series 11kV class On-load voltage regulation is a voltage regulation method by which a transformer can change the voltage
by changing the tap gear when operating under load. Power electronic component switches have the advantages of frequent switching, no spark and long service life,
so they can be used as on-load tap-changer for distribution transformers.
Standard
GB1094.1-2013; GB1094.2-2013; GB1094.3-2013; GB1094.5-2008; GB/T 6451-2008; GB/T 1094.10-2003; JB/T10088-2004
IEC60076; SANS 780 STANDARDS
Features of Products
1. Meet or exceeds ANSL. IEC. GB. SANS. Standards
2. Safe Handling, Installation and Operation.
3. Attractive, modern appearance
4. Reasonable Structure
5. Fully-sealed
6. Higher system reliability
7. High security and reliability in operation
8. High capacity of overload and efficiency
9. Robust construction having excellent short circuit and thermal withstand capabilities
10. EVERPOWER Transformers are more efficient by Reduced no-load losses and Reduced load losses
| SZ10 series 11kV distribution transformer technical data |
| Rated
Capacity
(kVA) |
Voltage Group
(kV) |
Vector
Group |
Impedance voltage |
Loss(kW) |
No-load
current |
Weight(kg) |
L*B*H(mm)
Outline dimension |
Gauge vertical
horizontal
(mm) |
| High
Voltage |
Low
Voltage |
% |
No-load |
Load |
% |
Machine
weight |
Oil
weight |
Gross
weight |
| 200 |
|
|
|
4 |
0.48 |
3.06 |
1.5 |
510 |
210 |
960 |
1440*780*1140 |
550/520 |
| 250 |
|
|
|
0.56 |
3.60 |
1.4 |
600 |
230 |
1105 |
1480*800*1200 |
650/550 |
| 315 |
13.8 |
|
|
0.67 |
4.32 |
1.4 |
690 |
260 |
1315 |
1600*860*1210 |
650/550 |
| 400 |
13.2 |
|
|
0.80 |
5.22 |
1.3 |
890 |
310 |
1570 |
1680*940*1300 |
650/550 |
| 500 |
11 |
0.4 |
Yyno |
0.96 |
6.21 |
1.2 |
990 |
310 |
1710 |
1660*1040*1310 |
750/600 |
| 630 |
|
0.415 |
Dyn11 |
4.5 |
1.20 |
7.65 |
1.1 |
1160 |
400 |
2050 |
1810*1140*1350 |
850*660 |
| 800 |
10.5 |
|
|
1.40 |
9.36 |
1.0 |
1430 |
430 |
2480 |
1890*1210*1380 |
850/660 |
| 1000 |
|
0.433 |
Dyn5 |
1.70 |
10.98 |
1.0 |
1530 |
540 |
2830 |
1950*1260*1510 |
850/660 |
| 1250 |
10 |
|
|
1.95 |
13.05 |
0.9 |
1800 |
610 |
3460 |
1960*1280*1660 |
850/660 |
| 1600 |
6 |
|
|
2.40 |
15.57 |
0.8 |
2200 |
700 |
4060 |
2350*1620*2020 |
850/700 |
| 2000 |
|
|
|
2.80 |
21.26 |
0.8 |
2460 |
800 |
4620 |
2460*1740*2050 |
820/820 |
| 2500 |
|
|
|
3.30 |
24.69 |
0.7 |
3070 |
910 |
5630 |
2650*1800*2100 |
1070/1070 |
Note:Tapping range of high-voltage:±5%,±2×2.5%; Frequency:50Hz
| SZ11 series 11kV distribution transformer technical data |
| Rated
Capacity
(kVA) |
Voltage Group
(kV) |
Vector
Group |
Impedance voltage |
Loss(kW) |
No-load
current |
Weight(kg) |
L*B*H(mm)
Outline dimension |
Gauge vertical
horizontal
(mm) |
| High
Voltage |
Low
Voltage |
% |
No-load |
Load |
% |
Machine
weight |
Oil
weight |
Gross
weight |
| 200 |
|
|
|
4 |
0.34 |
3.06 |
1.5 |
540 |
270 |
1110 |
1400*740*1190 |
550/520 |
| 250 |
|
|
|
0.40 |
3.60 |
1.4 |
640 |
290 |
1270 |
1420*790*1210 |
650/550 |
| 315 |
13.8 |
|
|
0.48 |
4.32 |
1.4 |
730 |
320 |
1500 |
1540*850*1240 |
650/550 |
| 400 |
|
|
|
0.57 |
5.22 |
1.3 |
940 |
370 |
1780 |
1590*940*1250 |
650/550 |
| 500 |
13.2 |
0.4 |
Yyno |
0.68 |
6.21 |
1.2 |
1040 |
370 |
1920 |
1650*1000*1350 |
750/600 |
| 630 |
11 |
|
Dyn11 |
4.5 |
0.81 |
7.65 |
1.1 |
1220 |
460 |
2280 |
1810*1200*1310 |
850/660 |
| 800 |
10.5 |
0.415 |
|
0.96 |
9.36 |
1.0 |
1500 |
500 |
2740 |
1860*1090*1500 |
850/660 |
| 1000 |
|
0.433 |
Dyn5 |
1.15 |
10.98 |
1.0 |
1610 |
520 |
3060 |
1910*1260*1570 |
850/660 |
| 1250 |
10 |
|
|
1.36 |
13.05 |
0.9 |
1880 |
700 |
3710 |
1960*1280*1740 |
850/660 |
| 1600 |
6 |
|
|
1.64 |
15.57 |
0.8 |
2290 |
780 |
4350 |
2330*1800*1910 |
850/700 |
| 2000 |
|
|
|
1.96 |
21.26 |
0.8 |
2560 |
900 |
4950 |
2580*1900*1950 |
820/820 |
| 2500 |
|
|
|
2.31 |
24.69 |
0.7 |
3170 |
1010 |
6020 |
2580*1940*2250 |
1070/1070 |
Note:It can supply voltage regulating range of ±4×2.5% for high-voltage on-load regulation transformer